12 kV Metal Clad ED15

Rated ValuesED15
Rated VoltagekV12
FrequencyHz50/60
Short-Duration Power Frequency Withstand VoltagekV28
Lightning Impulse Withstand VoltagekV75
Short-Circuit Breaking CurrentkA31,5
Short-Time Withstand Current, 3skA31,5
Short-Circuit Making CurrentkA79
Peak Withstand CurrentkA79
Normal Current of BusbarA2500
Normal Current of Feeders:
With Circuit-BreakerA2500
With Disconnector LinkA2500
Bus SectionalizerA2500
Busbar Connection PanelA2500
Altitude1000m
Operating temperature15 up to 55C